A pool holds the true state of the grid at every frame. The operator does not see the state. The operator sees meter readings, and each reading has an error. This page explains how the package turns a state into a scan: the meter plan, the measurement function and the noise.

The three classes are in src/fdia_graph/sensing/ and serve every test system.

Class File Holds
MeterPlan sensing/meters.py every meter, as one row of a table
Measurement sensing/measure.py the readings a state gives, and their Jacobian
NoiseModel sensing/noise.py each meter's error: a bias and a jitter

A benign scan is NoiseModel.sample(Measurement.h(state)). It needs no new solve: the readings follow from the stored state.

The meter plan

MeterPlan is a table with one row per meter.

Column Meaning
kind what the meter reads (MeterKind, below)
bus the bus it sits at
branch, end the branch and its end (0 from, 1 to); -1 for a bus meter
owner the client that owns the meter's bus
sigma_rel, sigma_abs the accuracy class
bias the meter's constant error

The plan is made once per timeline, from the seed. It is the same on every frame.

What a meter reads

The meters follow the SCADA and PMU plan of [WU26, eqs. 17-20]. A SCADA voltmeter reads the voltage magnitude only. A PMU reads the magnitude, the angle, and the current phasor of every branch end at its bus.

MeterKind Reads Unit
V voltage magnitude at a bus p.u.
VA voltage angle at a PMU bus degrees
P, Q power injection at a bus MW, MVAr
PF, QF power flow at one end of a branch MW, MVAr
IR, II PMU current as real and imaginary part p.u.

The placement

MeterPlan.from_coverage places the meters at random, on every test system.

Meter Where
P, Q injection every bus
P, Q flow the from end of a random share of branches
Voltmeters a random share of buses
PMUs a random share of buses, at least one
PMU currents every branch end at a PMU bus, as real and imaginary part
Owner one client; with the owners of the buses, the client of the meter's bus

MeterSettings gives the shares: vbus_frac 0.6, pmu_frac 0.2 and flow_frac 0.9. The voltmeter buses are int(0.6 N) buses drawn at random, the PMU buses max(1, int(0.2 N)). Each branch gets a flow meter with probability 0.9.

On the New York case the meters are drawn over all 140 buses, the neighbouring grids' included. A source built with own= gives each meter the client of its bus; a meter at a bus that belongs to no client has owner -1 (Generate a timeline).

import numpy as np

from fdia_graph.constants.meters import MeterKind
from fdia_graph.models.config import MeterSettings
from fdia_graph.sensing.meters import MeterPlan
from fdia_graph.systems.case import Case

case = Case.from_ieee(14)  # needs fdia-graph[generate]
rng = np.random.default_rng(0)
plan = MeterPlan.from_coverage(case, MeterSettings(), rng)
for kind in (MeterKind.V, MeterKind.VA, MeterKind.PF):
    print(kind.name, int((plan.kind == kind).sum()))
# V 10, VA 2, PF 17

The table and the file

In the code the readings of one frame are a flat vector z, one value per row of the plan. In a timeline file they are layers: one array per bus, per branch and per PMU current.

Method Does
MeterPlan.scatter puts one value per meter at its place in the layers
MeterPlan.gather reads the flat vector back from the layers
MeterPlan.from_masks rebuilds the table from the meter masks of a file that records the client of each bus

The round trip is exact. A client's data is the columns of z whose meter it owns.

The measurement function

Measurement.h(vm, va) gives the exact reading of every meter of the plan for a state: the voltage magnitudes vm (p.u.) and angles va (degrees). The flows and currents follow from the voltages through the admittances of the Network.

The injections can be taken two ways.

  • From the voltages. This is the default.
  • From the pool, passed as injections=. An IEEE pool stores its own injections, and the generator passes them.

Measurement.jacobian(vm, va) is the derivative of the readings with respect to the state. Measurement.for_client(c) is the same function over one client's meters.

from fdia_graph.sensing.measure import Measurement
from fdia_graph.sensing.noise import NoiseModel
from fdia_graph.systems.network import Network

# case, plan and rng: from the snippet above
measure = Measurement(Network(case), plan)
z = measure.h(case.vm, case.va)       # exact readings
scan = NoiseModel(plan).sample(z, rng)  # one noisy scan
print(z.shape, scan.shape)            # (86,) (86,)

Measurement.h computes an injection from the voltages as generation minus load. A file stores load as positive, the sign an IEEE pool uses (Data dictionary).

Accuracy classes

Each meter kind has an accuracy class: the standard deviation of its total error. The classes follow [ASP14] and are in constants/meters.py (ACCURACY_CLASS, KIND_ACCURACY).

Meter Standard deviation Kind of error
power injection and flow 1.7 % of the reading relative
voltage magnitude 0.0012 p.u. absolute
voltage angle 0.00168 rad absolute
PMU current 1/300 of the current's magnitude relative
PMU current angle 1/300 rad absolute

The PMU current class is the 1 % total vector error of IEEE C37.118.1 [C37118], taken as three standard deviations (PMU_CURRENT_CLASS). It is relative to the phasor's magnitude, on the real and the imaginary part alike.

A relative meter also has a floor, so a reading near zero still has noise: 0.001 MW or MVAr on a power meter (POWER_NOISE_FLOOR_MW) and 0.00001 p.u. on a current (CURRENT_FLOOR_PU).

MeterSettings.power_floor_pu sets the power meters' floor for a data set, per unit of the system base. None, the default, keeps 0.001 MW whatever the base. The SCADA noise of [WU26]'s case studies is a flat 0.03 p.u. (WU26_SCADA_NOISE_PU), which is 3 MW on a 100 MVA base. The floor is part of the noise every reading carries, so the ramp's stealth bound, the tamper count and the limit tolerance follow it (The attack families). A file made with a floor of its own records it in the attribute power_floor_mw, and fg.load, the clients' reader and the state estimator weight by the stored value. A file without the attribute has the package's own floor.

Bias and jitter

A meter's error is mostly a fixed calibration offset. The package splits each class in two.

Part Share of the class Drawn
jitter 0.25 (JITTER_FRAC) again at every scan
bias sqrt(1 - 0.25^2), about 0.97 once per meter, with the plan

The squares of the two shares add to 1 (0.25² + 0.97² = 1), so bias and jitter together have the standard deviation of the class. On a relative meter the bias is a gain error. On an absolute meter it is an offset.

The biases are drawn with the plan: one draw for every bus and branch, metered or not (MeterPlan.from_placement).

A reading is the exact value with its bias, plus the jitter of that scan (NoiseModel.sample). NoiseModel.sigmas(z) gives the total of both, which an estimator weights by.

Treating the whole class as per-scan noise would make consecutive scans jump more than real meters do, and would hide the slow changes a detector looks for.

How the noise is keyed

The jitter of frame t comes from the frame's own random stream, keyed by the seed, a fixed stream code (JITTER_STREAM in constants/streams.py) and the frame's position in the pool.

So the noise of a frame does not depend on which attacks are placed, nor on where the walk stops and starts. Two timelines built from one seed and one pool with different families carry the same benign scans. Only the attacks differ.

The biases are part of the plan, so they are fixed by the seed too.

What is not in a file

A timeline file stores the meter masks, not the table. It does not store each meter's accuracy class (the table KIND_ACCURACY gives it) or its bias (drawn from the seed).